IO-Link (IEC 61131-9) is a point-to-point connection between a master port and a single sensor or actuator. Besides the cyclic process data it carries parameters (read/write on demand) and events (diagnosis reported by the device). This page explains how to connect IO-Link devices to an Indel system, how to configure them and how they show up in INOS.
612564000) into a COP-PAS (GinLink) or a COP-MAS2 (COPBus).<IOLink> section with one <Port> per used port to the COP-IOL's user configuration (see Configuration).Minimal example, the device is detected automatically:
The COP-IOL (612564000) is the IO-Link master module of the COP family:
Number 0..7), each port connects exactly one IO-Link device.The COP-IOL is connected like any other COP module, either
| Bus master | Bus | User configuration file | Port name |
|---|---|---|---|
| COP-PAS | GinLink | the COP-PAS's cop0.xml (COP-IOL as nested <Card>) | COP0.IOL0.Distance |
| COP-MAS2 | COPBus | one xcfg file per COP module, e.g. xcfg-iol.xml | IOL0.Distance |
The port name (last column, for a COP-IOL named IOL0 and a port named Distance) identifies the port everywhere: in INCO, in the process image channel names and in the API (see Parameter access from the application).
The COP-IOL is a nested <Card> of the COP-PAS's user configuration (config/ginlink/cop0.xml). Address is the COP slot of the COP-IOL.
On the COPBus every COP module has its own user configuration file. The trans-table-name is the module name.
Complete, working examples are found in config_mcrobot_iolink/ginlink and config_mcrobot_iolink/copbus.
The <IOLink> section inside the COP-IOL's <Card> lists the ports to use. Ports that are not listed stay disabled. Changes take effect at the next bus start (GinLink: also after a rescan).
| Attribute | Required | Default | Description |
|---|---|---|---|
Number | yes | - | Port number on the COP-IOL, 0..7. |
Name | yes | - | Port name, last part of the port name (e.g. COP0.IOL0.Sensor6). Must be unique per COP-IOL. |
CycleTime | no | 10000000 | Master cycle time in ns (default 10 ms). 0 uses the device's MinCycleTime, the fastest cycle the device supports. Allowed: not faster than the device's MinCycleTime and 2 x the bus cycle time, not slower than 132.8 ms. The value is rounded up to a multiple of the bus cycle time. |
EventAcknowledge | no | auto | auto or manual, see Acknowledge: EventAcknowledge="auto" | "manual". |
The optional <Device> element tells which device is expected at the port.
| Attribute | Required | Description |
|---|---|---|
deviceId | no | IO-Link DeviceID (decimal) of the expected device. Missing or "auto": the device is detected automatically. |
vendorId | no | Informative only (VendorID of the device). |
vendorName | no | Informative only. |
At startup the port always reads the VendorID/DeviceID reported by the connected device. With that
<Device> element (or deviceId missing/"auto"): the connected device is identified by its DeviceID and set up with the matching IODD. Use this for "any device" ports or exchangeable devices.deviceId given: the connected device has to report exactly this DeviceID, otherwise the port stops with INOS_MCTARGET_IOLINK_DEVICEID_WRONG. Use this to detect wrongly plugged devices.In both cases the IODD for the DeviceID has to be part of the configuration (see Device description (IODD)), otherwise the port stops with INOS_MCTARGET_IOLINK_DEVICEID_UNKNOWN.
<Device> element is also where the process data channel names are configured. To combine own channel names with automatic detection, just omit deviceId.Everything INOS knows about a device - its parameters, process data layout, texts and event codes - comes from the device's IODD. Therefore:
config/iolink).IODD (or iodd) and end with .xml, e.g. Baumer-OG0xxUR_ID101005-20210121-IODD1.1.xml. This is how IODDs are recognized among the downloaded files.INOS_MCTARGET_IOLINK_DEVICEID_DUPLICATE).All loaded device types are listed in INCO under Target.resource.fieldbus.iolink.pool.
The process data of a device is mapped to process image channels, named <port name>.<item name>:
| IODD process data item | Process image channel |
|---|---|
BooleanT | digital input/output bit |
IntegerT | analog input (adc) / output (dac) channel |
UIntegerT | analog input (adc) / output (dac) channel, enum combo if the IODD defines SingleValues |
Float32T | analog input (adc) / output (dac) channel |
The item name is the IODD text of the item, or the name configured with a <Channel> element (see Texts and names). Example: the item "Measurement value" of the device at port COP0.IOL0.Sensor6 becomes the adc channel COP0.IOL0.Sensor6.Measurement value, or COP0.IOL0.Sensor6.Distance with the <Channel> example above.
Name check. Every item name is checked against the INCO naming guidelines: only letters, digits, spaces, _ and - are allowed. Periods are replaced by _ beforehand, in every channel name (from the IODD, a text data file or a <Channel> entry), because the process image would split the name at a period, even at an escaped one (\.). A name that still violates the guidelines (e.g. Temperature (°C) or On/Off) is used anyway, but reported with a trace:
By default this is a warning. With the iDev feature IO-Link > Strict channel names (ch.indel.inos.iolink.strictnames) it is an error, e.g. to enforce clean names in a release build.
On a warning or error, replace the default name by a valid one. The trace shows the text id and where the name comes from:
from IODD: add a <Channel> entry for this text id to the port's <Device> element (see Process data channel names in the COP-IOL configuration), or rename it for all devices of this type in a text data file (see Text data files).from config: fix the name attribute of the <Channel> entry (see Process data channel names in the COP-IOL configuration).If the IODD defines different process data layouts depending on a parameter (<ProcessData> with <Condition>), the parameter is read at startup and the matching layout is used.
The channels are updated every master cycle while the port is in state operate. They keep their names when a port is restarted or the bus is rescanned.
param contains one entry per IODD variable, records as folders with one entry per subindex, with the IODD's names, units, value ranges and value texts. Reading an entry reads it from the device, writing it writes it to the device.Parameters are addressed by port name, ISDU index and subindex (see the device's IODD or manual). Subindex 0 addresses the whole parameter/record.
INCO procedures of Target.resource.fieldbus.iolink:
| Procedure | Description |
|---|---|
paramget | Read a parameter (result as number or string). |
paramset | Write a parameter, number and string overload. |
portenable | Start a port again (e.g. after a device exchange). |
portdisable | Stop a port. |
Every port offers the same procedures without the port argument, below its INCO path in command:
| Procedure | Description |
|---|---|
paramget(index:l, subindex:l, "") | Read a parameter, returns its value (number or string). |
paramset(index:l, subindex:l, value:d, "") | Write a numeric parameter. |
paramset(index:l, subindex:l, "value", "") | Write a string parameter. |
Any INCO client can call these procedures. Example in Python, reading the temperature (index 86, V_DeviceTemperature) of the device on port COP0.IOL0.Sensor6 of target Net227:
Writing works the same way (:l marks integer, :d floating point arguments, strings are quoted):
IOLINK is the CINOSMcTargetIOLinkMaster singleton:
operate.The names shown in INCO and used for the process image channels, as well as the event texts, are taken from the IODD's text collection (primary language). They can be replaced without touching the IODD. For each text the first match wins:
<Channel> entry in the COP-IOL configuration (process data channel names only),ch.indel.iolink.device.<deviceId>.text.xml,Texts are referenced by their IODD text id. Look them up in the IODD:
A <Channel> element inside the port's <Device> element renames one process data channel. TextId is the text id of the process data item, name the new name.
Result: COP0.IOL0.Sensor6.Distance and COP0.IOL0.Sensor6.Present instead of COP0.IOL0.Sensor6.Measurement value and COP0.IOL0.Sensor6.Switch state SSC1.
Use this to give channels application specific names, which can differ for two equal devices on different ports.
A text data file replaces IODD texts for all devices with a given DeviceID: parameter names and descriptions in INCO, value texts of enum parameters, process data channel names and event texts. It's a standard INOS xml data file, the object id has to be ch.indel.iolink.device.<deviceId>.text and every <property> replaces the text with the given text id. Name the file like the object, e.g. ch.indel.iolink.device.101005.text.xml.
Typical uses: translations (the IODD's primary language is usually English), shorter or company specific names, or clearer event texts for the operator.
Devices report diagnosis as IO-Link events, e.g. "Temperature overrun" or "Maintenance required". Each event has a 16 bit EventCode (standard codes per IO-Link Annex D, or device specific ones defined in the IODD), a type and a mode.
Every event is logged and posted as INOS message with the message code 0x4044<EventCode> (INOS_IOLINK_EVENT_BASE + EventCode):
| Event type | Message type |
|---|---|
| Error | INOS_MCMSG_TYPE_ERROR |
| Warning | INOS_MCMSG_TYPE_WARNING |
| Notification | INOS_MCMSG_TYPE_INFO |
The message text is the event's text (IODD, text data file or standard EventCode text). The message carries an Info data object with the properties Text (event name) and Description (IODD event description, if any), which the application can display.
IO-Link messages are posted by the port tasks. To have them show up in the application's Machine message handling (folder Machine, message history, HMI), the machine module has to receive target messages. Set TgtMsg=Client in the machine's Param (e.g. applicat/lua/machine.dt2):
Without TgtMsg=Client the events are still logged, but the application doesn't see them as messages.
Events with mode appears / disappears describe a condition that comes and goes (e.g. over temperature). Events with mode single shot are a one-time notification.
| Event mode | EventAcknowledge="auto" (default) | EventAcknowledge="manual" |
|---|---|---|
| appears | message posted | message posted |
| disappears | the message posted on appears is acknowledged automatically | nothing, the message stays until the operator acknowledges it |
| single shot | message posted, operator acknowledges | message posted, operator acknowledges |
auto: the message list always shows the conditions that are present right now. Use it for conditions that just need to be visible.manual: the operator sees every condition that occurred, even if it was gone a moment later. Use it for conditions that need attention (e.g. short circuit, temperature fault).INOS_MCTARGET_IOLINK_DEVICE_MAX_32BIT_SUPPORTED otherwise).TYPE_2_1 .. TYPE_2_5 and TYPE_2_V only, i.e. devices with process data. Devices without process data (TYPE_0, TYPE_1_2, TYPE_1_V) and legacy V1.0 devices with more than 2 octets of process data (TYPE_1_1/1_2 interleaved) are rejected with INOS_MCTARGET_IOLINK_OPERATE_MSEQUENCE_NOT_SUPPORTED.OctetStringT, TimeT and TimeSpanT are not supported as parameters.| Symptom | Check |
|---|---|
Port stays inactive, INOS_MCTARGET_IOLINK_NO_SENSOR_DETECTED | No sensor connected to this port number, or the cable/supply is broken (the port draws no current). |
Port stays inactive, INOS_MCTARGET_IOLINK_ESTABLISH_COMM_TO_DEVICE_FAILED | Device connected to the right port number? Cable? Device supplied? |
INOS_MCTARGET_IOLINK_DEVICEID_UNKNOWN | IODD of this DeviceID missing in the configuration, or its file name doesn't contain IODD. The DeviceID read from the device is shown in the port's param folder (page1.deviceid). |
INOS_MCTARGET_IOLINK_DEVICEID_WRONG | Another device than configured is connected. Fix the config or use automatic detection. |
| Device works, but no IO-Link messages in the application | TgtMsg=Client missing in the machine config. |
Channel named ...TN_xxx | The IODD has no text for this text id. Add it to a text data file or a <Channel> entry. |
Trace channel name '...' violates the INCO naming guidelines | The default name contains invalid characters. Replace it, see name check. |
| Port runs, but no process data channels | The device has no process data, or more than 32 bits. Check the port's prop (processdatainoctets / processdataoutoctets). |
INOS_IOLINK_ISDU_* on parameter access | The device rejected the access, see Parameter access errors (0x4043xxxx). |
Reported by port enable (shown in the port's prop, logged and returned by portenable) or by parameter access.
| Code | Name (INOS_MCTARGET_IOLINK_...) | When |
|---|---|---|
| 0x403F6000 | GENERAL | Reserved, not raised currently. |
| 0x403F6001 | NOT_IMPLEMENTED | Reserved, not raised currently. |
| 0x403F6002 | PORT_UNKNOWN | API/INCO call with a port name that isn't configured. |
| 0x403F6003 | INDEX_INVALID | Parameter access to an index the IODD doesn't define; IODD defines an index twice (logged, second one ignored). |
| 0x403F6004 | SUBINDEX_INVALID | Parameter access to a subindex the IODD doesn't define; IODD defines a subindex twice (logged, second one ignored). |
| 0x403F6005 | DEVICEID_DUPLICATE | Two IODDs with the same DeviceID in the configuration, the second one is ignored. |
| 0x403F6006 | DEVICEID_MISSING | Reserved, not raised currently (a missing deviceId means automatic detection). |
| 0x403F6007 | DEVICEID_WRONG | Port enable: the connected device reports another DeviceID than configured. |
| 0x403F6008 | DEVICEID_UNKNOWN | Port enable: no IODD for the DeviceID of the connected device. |
| 0x403F6009 | DEVICE_NOT_CONNECTED | Parameter access to a port that isn't in operation (no device). |
| 0x403F600A | DEVICE_CYCLETIME_TOO_FAST | Port enable: CycleTime shorter than the device's MinCycleTime. |
| 0x403F600B | DEVICE_CYCLETIME_MIN_2MS | Port enable: CycleTime shorter than 2 x the bus cycle time. |
| 0x403F600C | DEVICE_CYCLETIME_SET_FAILED | Port enable: the device didn't accept the master cycle time. |
| 0x403F600D | DEVICE_MAX_32BIT_SUPPORTED | Port enable: device has more than 32 bits process data in or out. |
| 0x403F600E | PARAM_IS_NUMBER | String access (get/set) to a numeric parameter. |
| 0x403F600F | PARAM_IS_STRING | Numeric access (get/set) to a string parameter. |
| 0x403F6010 | PARAM_WRITE_ONLY | Read of a write-only parameter. |
| 0x403F6011 | PARAM_READ_ONLY | Write of a read-only parameter. |
| 0x403F6012 | PARAM_STR_MIN_LENGTH | String write shorter than the IODD's minimum length. |
| 0x403F6013 | PARAM_STR_MAX_LENGTH | String write longer than the IODD's maximum length. |
| 0x403F6014 | PARAM_NBR_MIN | Numeric write below the IODD's value range. |
| 0x403F6015 | PARAM_NBR_MAX | Numeric write above the IODD's value range. |
| 0x403F6016 | PARAM_WRITE_SIZE | Write of more than 1 byte to the direct parameter page. |
| 0x403F6017 | PARAM_INDEX_NOT_SUPPORTED | Access to a record that can only be accessed as a whole, but is too large (> 64 bits). |
| 0x403F6018 | PARAM_ISDU_NOT_SUPPORTED | Access to an ISDU index of a device without ISDU support. |
| 0x403F6019 | COMM_CHECKSUM_ERROR | Frame with checksum error during startup. |
| 0x403F601A | COMM_SEND_TIMEOUT | Frame couldn't be sent during startup (hardware). |
| 0x403F601B | COMM_RECEIVE_TIMEOUT | No answer from the device during startup. |
| 0x403F601C | COMM_CMD_UNKNOWN | Internal error. |
| 0x403F601D | OPERATE_MSEQUENCE_NOT_SUPPORTED | Port enable: the device's operate M-sequence type isn't supported (see Limitations). |
| 0x403F601E | ESTABLISH_COMM_TO_DEVICE_FAILED | Port enable: wake-up failed, no device answered within 2 s. |
| 0x403F601F | ESTABLISH_COMM_INVALID_BAUDRATE | Port enable: device answered with an unknown transmission rate. |
| 0x403F6020 | IODD_PARSE_ERROR | Configuration: an IODD file isn't valid xml (logged with line/column). |
| 0x403F6021 | IODD_INVALID | Configuration: an IODD file has no valid device identity. |
| 0x403F6022 | PARAM_PAGE_WRITE_NOT_IN_OPERATE | Write to the direct parameter page while the port is in operate. |
| 0x403F6023 | PROCESSDATA_VARIANT_UNRESOLVED | Port enable: the IODD's process data layout depends on a parameter that couldn't be read. |
| 0x403F6024 | DEVICE_MINCYCLETIME_INVALID | Port enable: the device reports a MinCycleTime with a reserved time base. |
| 0x403F6025 | DEVICE_CYCLETIME_TOO_SLOW | Port enable: CycleTime longer than 132.8 ms (the longest cycle time IO-Link can encode). |
| 0x403F6026 | NO_SENSOR_DETECTED | Port enable: no current drawn on the port within 1000 ms after power-on, i.e. no sensor connected (or cable/supply problem). |
Parameter access (ISDU) errors. The master detected ones are:
| Code | Name (INOS_IOLINK_ISDU_...) | When |
|---|---|---|
| 0x40431000 | COMM_ERROR | No valid answer from the device (device gone, GinLink down). |
| 0x40431100 | TIMEOUT | The device kept answering "busy" for too long. |
| 0x40435600 | CHECKUM_ERROR | ISDU answer with checksum error (after retries). |
| 0x40435700 | ILLEGAL_SERVICE | Reserved, not raised currently. |
If the device rejects an access, its IO-Link ErrorType (Annex C) is returned as 0x4043<ErrorCode><AdditionalCode>, e.g.:
| Code | Name (INOS_IOLINK_ISDU_...) | Meaning |
|---|---|---|
| 0x40438000 | DEVICE_APPLICATION_ERROR | Device application error, no details. |
| 0x40438011 | INDEX_NOT_AVAILABLE | Index not available in the device. |
| 0x40438012 | SUBINDEX_NOT_AVAILABLE | Subindex not available in the device. |
| 0x40438020 | SERVICE_TEMP_NOT_AVAILABLE | Service temporarily not available. |
| 0x40438021 | SERVICE_TEMP_NOT_AVAILABLE_LOCAL | Temporarily not available, local operation at the device. |
| 0x40438022 | SERVICE_TEMP_NOT_AVAILABLE_DEVICE | Temporarily not available, device control (e.g. teach-in running). |
| 0x40438023 | ACCESS_DENIED | Write to a read-only index. |
| 0x40438030 | PARAMETER_VALUE_OUT_OF_RANGE | Value out of range. |
| 0x40438031 | PARAMETER_VALUE_ABOVE_LIMIT | Value above limit. |
| 0x40438032 | PARAMETER_VALUE_BELOW_LIMIT | Value below limit. |
| 0x40438033 | PARAMETER_LENGTH_OVERRUN | Data too long. |
| 0x40438034 | PARAMETER_LENGTH_UNDERRUN | Data too short. |
| 0x40438035 | FUNCTION_NOT_AVAILABLE | Command not supported by the device. |
| 0x40438036 | FUNCTION_TEMP_UNAVAILABLE | Command temporarily unavailable. |
| 0x40438040 | INVALID_PARAM_SET | Conflicting parameter (single parameter). |
| 0x40438041 | INCONSISTENT_PARAM_SET | Parameter set inconsistent (block parameterization). |
| 0x40438082 | APPLICATION_NOT_READY | Device application not ready. |
| 0x40438100 | UNSPECIFIC | Vendor specific, codes 0x8101.. are defined by the device manual. |
Event messages carry 0x4044<EventCode>. Device specific EventCodes get their text from the IODD (or a text data file), the standard EventCodes (IO-Link Annex D) are predefined:
| Code | Name (INOS_IOLINK_EVENT_...) | Meaning |
|---|---|---|
| 0x40440000 | BASE | No malfunction. |
| 0x40441000 | GENERAL_MALFUNCTION | General malfunction, unknown error. |
| 0x40444000 | TEMPERATURE_FAULT | Temperature fault, overload. |
| 0x40444210 | TEMPERATURE_OVERRUN | Device temperature overrun. |
| 0x40444220 | TEMPERATURE_UNDERRUN | Device temperature underrun. |
| 0x40445000 | HARDWARE_FAULT | Device hardware fault. |
| 0x40445010 | COMPONENT_MALFUNCTION | Component malfunction. |
| 0x40445011 | NVM_LOSS | Non volatile memory loss. |
| 0x40445012 | BATTERIES_LOW | Batteries low. |
| 0x40445100 | POWER_SUPPLY_FAULT | General power supply fault. |
| 0x40445101 | FUSE_BLOWN | Fuse blown/open. |
| 0x40445110 | PRIMARY_VOLTAGE_OVERRUN | Primary supply voltage overrun. |
| 0x40445111 | PRIMARY_VOLTAGE_UNDERRUN | Primary supply voltage underrun. |
| 0x40445112 | SECONDARY_VOLTAGE_FAULT | Secondary supply voltage fault. |
| 0x40446000 | SOFTWARE_FAULT | Device software fault. |
| 0x40446320 | PARAMETER_ERROR | Parameter error. |
| 0x40446321 | PARAMETER_MISSING | Parameter missing. |
| 0x40447700 | WIRE_BREAK | Wire break of a subordinate device (0x7701..0x770F: device 1..15). |
| 0x40447710 | SHORT_CIRCUIT | Short circuit. |
| 0x40447711 | GROUND_FAULT | Ground fault. |
| 0x40448C00 | APPLICATION_FAULT | Technology specific application fault. |
| 0x40448C01 | SIMULATION_ACTIVE | Simulation active. |
| 0x40448C10 | PROCESS_VAR_OVERRUN | Process variable range overrun. |
| 0x40448C20 | MEASUREMENT_RANGE_EXCEEDED | Measurement range exceeded. |
| 0x40448C30 | PROCESS_VAR_UNDERRUN | Process variable range underrun. |
| 0x40448C40 | MAINTENANCE_CLEANING | Maintenance required, cleaning. |
| 0x40448C41 | MAINTENANCE_REFILL | Maintenance required, refill. |
| 0x40448C42 | MAINTENANCE_EXCHANGE_PARTS | Maintenance required, exchange wear and tear parts. |